0
sf6 outdoor circuit breaker
sf6 outdoor circuit breaker
sf6 outdoor circuit breaker

10kV MV Outdoor SF6 Circuit Breaker, LW3-12(G)ⅠⅡⅢ

EXLW3-12(G)ⅠⅡⅢ
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description
EXLW3-12, LW3-12(G) outdoor SF6 circuit breaker is a new type outdoor appliance which use SF6 gas as the medium for arcing and insulating. Its operation mechanism including (type I) manually energy-stored spring operation mechanism, (type II) automatical energy-stored spring operation mechanism and (type III) DC electromagnetic operation mechanism. These mechanisms and circuit breaker itself form a perfect whole. Compares to other outdoor circuit breaker in rated 12kV, this product has several advantages such as simple structure, excellent arc-extinguishing and insulating capacity, small working frequency, high rated parameter, long service life and less maintenance, which can not only reduce the floor space but also deduct the project cost and eliminate the fire hazards.

2. Main technical parameter

Item

Unit

Data

Rated voltage

kV

12

Max. working voltage

kV

12

Rated insulation level(when the short circuit is filled with SF6 gas was 0.25Mpa,20℃) lightning impulse withstand voltage(peak)

kV

75

Rated insulation level(when the short circuit is filled with SF6 gas was 0.25Mpa,20℃) 1 min P.F. withstand voltage

kV

42

Rated insulation level(when the short circuit is filled with SF6 gas was 0.25Mpa,20℃) rain test

kV

34

Rated insulation level(when the short circuit is filled with SF6 gas was 0.25Mpa,20℃) inverting impulse withstand voltage

kV

85

Insulation level under zero gauge pressure P.F. withstand voltage 1 min

kV

30

Insulation level under zero gauge pressure inverting-phase withstand voltage 1 min

kV

30

Insulation level under zero gauge pressure max. phase voltage 5 min

kV

12

Rated current

A

400, 630

Rated short-circuit breaking current

kA

6.3    8    12.5

Breaking current under zero gauge pressure

A

400    630

Rated operating sequence(type I)

O-180s-CO-180s-CO

Rated operating sequence(type II III)

O-0.3s-CO-180s-CO

Rated closing current( peak)

kA

16    20    31.5

Rated dynamic stability current(peak)

kA

16    20    31.5

Rated thermal stability current

kA

6.3    3    12.5

Rated thermal stability times

s

4

Send Message