mv circuit breaker

35kV MV Outdoor SF6 Circuit Breaker, LW8-40.5/2000-40

EXLW8-40.5/2000-40
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description
a. The circuit breaker is outdoor small ceramic column structure, which equipped with CT14 spring operation mechanism; mechanism and main part connected with simple installation. It has features of convenient adjustment, reliable operation, suitable for frequent operation; mechanism service life more than 3000 times;

b. Adopt air-compression arc-extinguishing structure, with strong breaking capacity, 40kA total breaking times up to 12, which is the highest in China;

c. Reliable sealing performance. Adopt import seal; dynamic seal adopts"V"type sealing ring with spring pressure compensation structure; the transformer secondary wiring board matched by cooperative enterprises, to ensure the annual leakage rate less than 1 %;

d. Inner current transformer adopts micro crystallizing alloy high magnetic materials, with accurate class up to grade 0.2 or grade 0.2S. According to users' needs, it can be matched with 12 transformers, to meet the load line of 50 km without restrike.

2. Main technical parameter

Item

Unit

Data

Technical parameter

Rated voltage

kV

40.5

Rated insulation level lightning impulse withstand voltage(peak)

kV

185

Rated insulation level 1 min P.F. withstand voltage

kV

95

Rated current

A

2000

Mechanical life time

time

3000

Rated air pressure of SF6(psig at 20℃)

Mpa

0.05

Alarm pressure/Min.function pressure (psig at 20℃)

Mpa

0.47/0.45

Rated short-circuit breaking current

kA

40

Rated short circuit making current(peak value)

kA

100

Rated short-time withstand current(thermal stability current)

kA

40

Rated peak withstand current(dynamic stability current)

kA

100

Rated out of step breaking current

kA

10

Rated breaking times under short circuit breaking current

time

12

Rated short circuit duration

S

4

Closing time(under rated operation voltage)

S

≤0.1

Opening time(under rated operation voltage)

S

≤0.06

Rated operating sequence

O-0.3s-CO-180s-CO

Rated making single capacitor bank current

A

400

Annual leakage rate

%

≤1

SF6 water content(V/V)

≤150×10-6

Rated operation voltage of matched CT14 spring operation mechanism

Closing and opening coil voltage

V

AC:220 380 DC:48 110 220

Energy storage motor voltage

V

AC:220 380 DC:110 220

Weight of SF6 gas

kg

8

Weight of circuit breaker(including operation mechanism)

kg

1400

Moving contact travel

mm

95±2

Measure moving contact travel

Opening distance between contacts

mm

60±1.5

Measure distance between moving and fixed contact

Pole-to-pole closing synchronous

ms

≤3

Measure pole distance difference between moving and fixed contact

Pole-to-pole opening synchronous

ms

≤2

Measure pole distance difference between moving and fixed contact

Main circuit resistance

≤120

Measure DC voltage reduction

Closing speed

m/s

3.2±0.2

Rated air pressure, measuring method

Opening speed

m/s

3.4±0.2

Rated air pressure, measuring method

Closing buffer distance

mm

10+0.5(-1.0)

Under closing state

Spacer of closing buffer

mm

1-2

Under closing state

Partial 48.6kV

Pc

20

Measure by partial measuring device under rated air pressure; apply voltage 48.6kV on the two out-line ends of the circuit breaker for 1 min, then reduce the voltage to 28kV to measure

Discharge 28kV

Pc

10