0
12kV/24kV High Voltage Switchgear
12kV/24kV High Voltage Switchgear
12kV/24kV High Voltage Switchgear
12kV/24kV High Voltage Switchgear
12kV/24kV High Voltage Switchgear

Armored Removable AC Metal Enclosed Switchgear,KYN28A-12/24

EXKYN28A-12/24
Quantity:
Contact Now
add to cart
PRODUCT  DESCRIPTION
EXKYN28A-12/24kV(GZS1)type armored removable AC metal-enclosed switchgear (hereinafter referred to as"switchgear"} is suitable for three-phase AC 50Hz power system for receiving and distributing power and controlling,protecting and monitoring of the circuit in real time.The newly introduced and developed large current and high breaking switchgear can also he used as a high-voltage generator export.
The product is in line with GB3906"3-35KVAC metal enclosed switchgear".GB/T11022"common technical requirements of high-voltage switchgear and control equipment standard",IEC62271"AC metal-enclosed switchgear and control equipment with rated voltage 1kV above 52kV and below"
The Technical Specifications of this KYN28A-12/24 Switchgear define its electrical and mechanical parameters for medium-voltage power distribution applications. The Armored Removable Metal Enclosed Switchgear is suitable for three-phase AC 50Hz power systems for receiving and distributing power, and for controlling, protecting, and monitoring circuits in real time. This 12kV/24kV High Voltage Switchgear is a newly introduced and developed large current and high breaking switchgear that can also be used as a high-voltage generator outlet. The KYN28A-12/24 Switchgear complies with GB3906"3-35kV AC metal enclosed switchgear", GB/T11022, and IEC62271 standards. This Armored Removable Metal Enclosed Switchgear features rated circuit breaker currents ranging from 630A to 4000A, with rated short-time withstand currents of 16, 20, 25, 31.5, 40, and 50kA. The 12kV/24kV High Voltage Switchgear offers rated short circuit breaking currents matching these values and rated peak withstand currents up to 125kA. Each KYN28A-12/24 Switchgear provides power frequency withstand voltages between poles of 24, 32, and 42kV, and lightning impulse withstand voltages of 40, 60, and 75kV, ensuring reliable operation in 12kV and 24kV distribution networks.
THE MAIN TECHNICAL PARAMETERS
ltemUnitData
Rated power supplykV3.6、7.2、12、24
Rate frequencyHz50 
Rated current of circuit breakerA630、1250、1600.2000、2500.3150、4000
Rated current of switchgearA630、1250、 1600、2000、2500、3150.4000
Rated short-time withstand current(4s)kA16、20、25、31.5、40、50
Rated peak withstand current(peak)kA40,50、63、80、100、125
Rated short circuit breaking currentkA16、20、25、315、40、50
Rated short circuit closing current(peak)kA40.50、63、80、100、125
Rated
insulation
level
1min power frequency
withstand voltage
Between the poleskV24、32、42
Between fractureskV24、32、48
Lightning impose
withstand voltage
(peak)Between
Between the poleskV40.60、75
Between the poleskV46、70,85
Protection classThe enclosure is IP4X,compartment,
and the circuit breaker compartment is IP2X
when the dooris open.
Note:1.The  short-circuit  capacity  of  the  current  transformer  should  he  considered  separately:
2.See VAC63A-12 technical parameters in the corresponding sample.
3.1000m-altitude   rated   current≤1250A    rated    breaking    current≤31.5kA.

Send Message