VAC-SRM-12/24 Ring Main Unit
VAC-SRM-12/24 Ring Main Unit
VAC-SRM-12/24 Ring Main Unit
VAC-SRM-12/24 Ring Main Unit
VAC-SRM-12/24 Ring Main Unit

Insulated Metal-enclosed Combined Electrical RMU, Load break switch Unit:C,Load switch fuse combination electrical unit:F; vacuum circuit breaker Unit:V

EX-SRM-12/24/36(40.5)
Quantity:
Contact Now
add to cart
Insulated Metal-enclosed Combined Electrical RMU
PRODUCT  DESCRIPTION
VAC-SRM-12/24 series of RMU is SF6 gas-insulated metal common tank enclosed switchgear, consisting of load break switch unit, load break switch fuse combination electrical unit, vacuum circuit breaker unit, and the incoming line unit of bus. It adopts a range of advanced technologies and materials, with excellent electrical and mechanical properties, less affected by environment and climate, in small size, easy to install, easy to operate, with no need of maintenance, and can  be flexibly combined, Its clear and intuitive design ensures simple and direct operation, the feeder's connection capacity is large, suitable for a variety of wiring systems.
The Technical Specifications of this SF6 Gas Insulated RMU define its electrical and mechanical parameters for medium-voltage distribution networks. The VAC-SRM-12/24 Ring Main Unit is an SF6 gas-insulated metal common tank enclosed switchgear, consisting of load break switch units, load break switch fuse combination electrical units, vacuum circuit breaker units, and bus incoming line units. This Load Break Switch Fuse Combination Unit adopts a range of advanced technologies and materials, delivering excellent electrical and mechanical properties with minimal environmental and climate impact. The SF6 Gas Insulated RMU features a compact design, easy installation, simple operation, maintenance-free performance, and flexible combination options. The VAC-SRM-12/24 Ring Main Unit offers unit configurations including C (standard single casing load break switch unit), F (load break switch and fuse combination), V (vacuum circuit breaker unit), D (cable unit without switch), SL (bus coupler unit), M (metering unit), and PT (voltage transformer unit). This Load Break Switch Fuse Combination Unit supports double-sleeve outgoing load break switch configurations (1K2/4). Each SF6 Gas Insulated RMU provides large feeder connection capacity suitable for a variety of wiring systems, with clear and intuitive design ensuring simple and direct operation.
UNIT DEFINITION
Unit codeMeaning
CStandard single casing load break switch unit
FLoad break switch and fuse combination
VApparatus unit
DCable unit(without switch)
+Side casing of busbar
-Top casing of busbar
SLBus couple unit
MMetering unit
PTPT unit
1K2(4)Double-sleeve outgoing load break switch unit
 
TECHNICAL SPECIFICATION
SF6 insulated ring main unit
 
ltemUnitLoad breakCombinationFuse unit
switch unitapparatus
Rated voltagekV12/24/36(40.5)12/24/36(40.5)12/24/36(40.5)
Rated frequencyHz50 50 50 
Rated currentA630 Depend on rated current of fuse630 
P.F.withstand voltage42/6542/6542/65
(phase to phase,phase to earth)
Ated    
insulation    
levels
P,F.withstand voltage48/7948/7948/79
(Across open contacts)
P.F.withstand voltagekV2/2212 2/2
(Control and auxiliary circuit)
Lightning impulse withstand voltage75/12575/12575/125
(phase to phase,phase to earth)
Across open contacts85/14585/14585/145
Ogauge pressure testPassPassPass
Rated short time withstand currentkA20/4s/20/3s20/4s/20/4s
Rated peak withstand currentA6363
Rated short circuit making currentkA50 or63Subject to high-voltage fuse  50 
Rated short circuit breaking currentkASubject to high-voltage fuse20/20
Rated transform currentA1750/1400630 
A630
Rated active load breaking currentA630
Rated Closed loop breaking currentTime
Mechanical lifeLoad break switch/breaker5000 5000
Isolating switch/earthing switch5000 5000 5000 
    Loop resistanceμΩ≤1201.3 ≤120
Inflation pressureRated infation pressure(absolute pressure)1.31.3
Minimum inflation pressurehar1.2 1.2 1.2 
(absolute pressure)
Relative rate leakage of gas%
0.02 0.02 0.02 
Remark;1:Neutral point earthing system through low resistance
II:Neutral point earthing/non-earthing system through arc suppression coil
 
Normal ambient conditionsSf6 pressure0.4bar,below 20℃
 Ambient temperatureLeakage rate peryear<0.25%/year
 Maximum temperature+50℃Protection degree
  24hours average+35℃SF6 gas chamberIp67
  Minimum temperature -40℃ Switchgear cover Ip67
 Humidity
 Maximum relative
 Average humidity
 
 
 Load break switch Unit:C
PRODUCT OVERVIEW
The switch can be divided into single body,single body double casing outgoing line,two unit,three unit,four unit,five unit standard type,and with side inlet casing type.It adopts a structure that shares one SF6 gas box,and does not require external bus connection between each unit.Therefore,the structure is relatively simplified,easy to install,and more safe; Although the integrated structure of the air box is adopted,each unit still has independent intervals.
Six units or more are achieved by using insulated bus bars in parallel cabinets,which can be combined in front,back,or left and right directions.The cabinet type is a standard type with bus sleeves on the upper side.
 
STANDARD CONFIGURATION
●630A  busbar

 Three position load/grounding switch

Spring  operating  mechanism

Position indication of load switch and grounding switch

Outgoing conduit horizontally arranged at the front

 Incoming/busbar voltage indicator(single or busbar expansion type)

●Output  voltage  indicator

●All switch functions can be controlled by adding a padlock on the panel

 Interlocking between grounding switch and cable compartment  door

SF6 pressure gauge

●Grounding copper bar

 Explosion proof pressure relief valve

OPTIONAL CONFIGURATION

Short  circuit,ground  fault   indicator

●Ring current transformers and ammeters for measurement

Ring current transformer for metering

Switch  position  keylock

 Electric operating mechanism

 Reserved busbar extension

 External busbar

Load switch fuse combination electrical unit:F

PRODUCT OVERVIEW

The combined electrical unit is used for transformer protection with a capacity of 1250KVAR and below.This unit is equipped with an insulation sleeve that can be installed into a fuse.The insulation sleeve is placed inside the SF6 gas box to further improve its insulation performance.When the grounding switch is closed,the lower side of the fuse is grounded simultaneously,and the safety isolation between the upper side of the fuse and the power supply is achieved to ensure thee safety of personnel when replacing the fuse.
In order to ensure that the fuse does not cause the electrical equipment to run out of phase after one phase is blown,a trip linkage mechanism is configured in this unit.When the trip observation window displays red,it indicates that the trip device is operating or the fuse is blown and tripped.This unit can be combined with other units to achieve ring network power supply.

STANDARD  CONFIGURATION

●630A  busbar

Three position load/grounding switch

Spring  operating  mechanism

Position indication of load switch and grounding switch

Outgoing conduit horizontally arranged at the front

 Incoming/busbar voltage indicator(single or busbar expansion type)

Output  voltage  indicator

●All switch functions can be controlled by adding a padlock on the panel

 Interlocking between grounding switch and cable compartment  door

SF6 pressure gauge

●Grounding copper bar

 Explosion proof pressure relief valve

 
OPTIONAL CONFIGURATION

Optional    configuration

Short  circuit,ground  fault   indicator

●Ring current transformers and ammeters for measurement

Ring current transformer for metering

●Switch position keylock

 Electric operating mechanism

 Reserved busbar extension

 External busbar

 
Vacuum circuit breaker Unit:V
 
PRODUCT OVERVIEW
Using spring type vacuum circuit breaker.The mechanical life can reach 5000 times;(The protection action is fast,and the opening time is not more than 30ms),making it easy to achieve differential coordination.
Using a three-position load isolation switch instead of a regular isolation switch can break the normal load current in special circumstances,improving product reliability.
The vacuum circuit breaker and load switch are sealed together in an SF6 gas box made of 3mm thick stainless steel plate, achieving full insulation,sealing,and maintenance free throughout the entire system.
 
STANDARD  CONFIGURATION

●630A  busbar

●630A circuit breaker module ISM

Controller CM (DC24V operating power supply)

● Three position load isolation switch

Self powered electronic electromechanical protector (SEG-WIM1,WIC1)

 Bushing protection CT

●Sf6 pressure gauge

 Bushing for load DIN47636 standard

●Grounding and locking of cable compartment doors

●Auxiliary contact for vacuum circuit breaker switch position:2NO+2NC

 Standard operating power supply(including power PT, power  module,backup  battery)

OPTIONAL   CONFIGURATION

Connecting   busbar

● Current transformers and ammeters for measurement

Auxiliary   contact:

Load isolation switch position 2NO+2NC

 Grounding switch position 2NO+2NC