Category
Insulated Metal-enclosed Combined Electrical RMU, Load break switch Unit:C,Load switch fuse combination electrical unit:F; vacuum circuit breaker Unit:V
| Unit code | Meaning | |||
| C | Standard single casing load break switch unit | |||
| F | Load break switch and fuse combination | |||
| V | Apparatus unit | |||
| D | Cable unit(without switch) | |||
| + | Side casing of busbar | |||
| - | Top casing of busbar | |||
| SL | Bus couple unit | |||
| M | Metering unit | |||
| PT | PT unit | |||
| 1K2(4) | Double-sleeve outgoing load break switch unit | |||
| ltem | Unit | Load break | Combination | Fuse unit | |||
| switch unit | apparatus | ||||||
| Rated voltage | kV | 12/24/36(40.5) | 12/24/36(40.5) | 12/24/36(40.5) | |||
| Rated frequency | Hz | 50 | 50 | 50 | |||
| Rated current | A | 630 | Depend on rated current of fuse | 630 | |||
| P.F.withstand voltage | 42/65 | 42/65 | 42/65 | ||||
| (phase to phase,phase to earth) | |||||||
Ated insulation levels | P,F.withstand voltage | 48/79 | 48/79 | 48/79 | |||
| (Across open contacts) | |||||||
| P.F.withstand voltage | kV | 2/2 | 212 | 2/2 | |||
| (Control and auxiliary circuit) | |||||||
| Lightning impulse withstand voltage | 75/125 | 75/125 | 75/125 | ||||
| (phase to phase,phase to earth) | |||||||
| Across open contacts | 85/145 | 85/145 | 85/145 | ||||
| Ogauge pressure test | Pass | Pass | Pass | ||||
| Rated short time withstand current | kA | 20/4s/20/3s | 20/4s/20/4s | ||||
| Rated peak withstand current | A | 63 | 63 | ||||
| Rated short circuit making current | kA | 50 or63 | Subject to high-voltage fuse | 50 | |||
| Rated short circuit breaking current | kA | Subject to high-voltage fuse | 20/20 | ||||
| Rated transform current | A | 1750/1400 | 630 | ||||
| A | 630 | ||||||
| Rated active load breaking current | A | 630 | |||||
| Rated Closed loop breaking current | Time | ||||||
| Mechanical life | Load break switch/breaker | 5000 | 5000 | ||||
| Isolating switch/earthing switch | 5000 | 5000 | 5000 | ||||
| Loop resistance | μΩ | ≤120 | 1.3 | ≤120 | |||
| Inflation pressure | Rated infation pressure(absolute pressure) | 1.3 | 1.3 | ||||
| Minimum inflation pressure | har | 1.2 | 1.2 | 1.2 | |||
| (absolute pressure) | |||||||
| Relative rate leakage of gas | % | ||||||
| 0.02 | 0.02 | 0.02 | |||||
| Remark; | 1:Neutral point earthing system through low resistance | ||||||
| II:Neutral point earthing/non-earthing system through arc suppression coil | |||||||
| Normal ambient conditions | Sf6 pressure | 0.4bar,below 20℃ | |||||
| Ambient temperature | Leakage rate peryear | <0.25%/year | |||||
| Maximum temperature | +50℃ | Protection degree | |||||
| 24hours average | +35℃ | SF6 gas chamber | Ip67 | ||||
| Minimum temperature | -40℃ | Switchgear cover | Ip67 | ||||
| Humidity | |||||||
| Maximum relative | |||||||
| Average humidity | |||||||
● Three position load/grounding switch
●Spring operating mechanism
●Position indication of load switch and grounding switch
●Outgoing conduit horizontally arranged at the front
● Incoming/busbar voltage indicator(single or busbar expansion type)
●Output voltage indicator
●All switch functions can be controlled by adding a padlock on the panel
● Interlocking between grounding switch and cable compartment door
●SF6 pressure gauge
●Grounding copper bar
● Explosion proof pressure relief valve
OPTIONAL CONFIGURATION
●Short circuit,ground fault indicator
●Ring current transformers and ammeters for measurement
●Ring current transformer for metering
●Switch position keylock
● Electric operating mechanism
● Reserved busbar extension
● External busbar
Load switch fuse combination electrical unit:F
PRODUCT OVERVIEW
The combined electrical unit is used for transformer protection with a capacity of 1250KVAR and below.This unit is equipped with an insulation sleeve that can be installed into a fuse.The insulation sleeve is placed inside the SF6 gas box to further improve its insulation performance.When the grounding switch is closed,the lower side of the fuse is grounded simultaneously,and the safety isolation between the upper side of the fuse and the power supply is achieved to ensure thee safety of personnel when replacing the fuse.
In order to ensure that the fuse does not cause the electrical equipment to run out of phase after one phase is blown,a trip linkage mechanism is configured in this unit.When the trip observation window displays red,it indicates that the trip device is operating or the fuse is blown and tripped.This unit can be combined with other units to achieve ring network power supply.
STANDARD CONFIGURATION
●630A busbar
●Three position load/grounding switch
●Spring operating mechanism
●Position indication of load switch and grounding switch
●Outgoing conduit horizontally arranged at the front
● Incoming/busbar voltage indicator(single or busbar expansion type)
●Output voltage indicator
●All switch functions can be controlled by adding a padlock on the panel
● Interlocking between grounding switch and cable compartment door
●SF6 pressure gauge
●Grounding copper bar
● Explosion proof pressure relief valve
●Optional configuration
●Short circuit,ground fault indicator
●Ring current transformers and ammeters for measurement
●Ring current transformer for metering
●Switch position keylock
● Electric operating mechanism
● Reserved busbar extension
● External busbar
Using a three-position load isolation switch instead of a regular isolation switch can break the normal load current in special circumstances,improving product reliability.
The vacuum circuit breaker and load switch are sealed together in an SF6 gas box made of 3mm thick stainless steel plate, achieving full insulation,sealing,and maintenance free throughout the entire system.
●630A busbar
●630A circuit breaker module ISM
●Controller CM (DC24V operating power supply)
● Three position load isolation switch
●Self powered electronic electromechanical protector (SEG-WIM1,WIC1)
● Bushing protection CT
●Sf6 pressure gauge
● Bushing for load DIN47636 standard
●Grounding and locking of cable compartment doors
●Auxiliary contact for vacuum circuit breaker switch position:2NO+2NC
● Standard operating power supply(including power PT, power module,backup battery)
OPTIONAL CONFIGURATION
●Connecting busbar
● Current transformers and ammeters for measurement
●Auxiliary contact:
●Load isolation switch position 2NO+2NC
● Grounding switch position 2NO+2NC