0
indoor vacuum circuit breaker
indoor vacuum circuit breaker
indoor vacuum circuit breaker
indoor vacuum circuit breaker

10kV MV Indoor Vacuum Circuit Breaker/VCB for Switchgear

EX63(VS1)-12kV
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description
    VAC63(VS1)1-12 indoor M.V. vacuum circuit breaker is an indoor switchgear with tri-phase AC 50Hz, rated voltage of 12kV, control and protection for industrial and mining enterprises, power plants and substations, electrical facilities and for frequent operation place adopting VET operating mechanism and circuit breaker integrated design can be used as a fixed installation unit can also be equipped with special advance mechanism, the composition of handcart unit used some of the main circuit can use the whole solid seal post with high reliability, maintenance free, in order to achieve smaller circuit breakers, can be equipped with KYN2BA 12(GZS) and other handcart switch cabinet. In the home it can also be used with fixed XGN switchgear.
    VAC63 is regular type mechanism, VAC83 is improved on the basis of VAC63. All VAC83 mechanisms can be replaced by VAC63 mechanisms, they are universal mechanism.

2. Main technical parameter

Item

Unit

Data

Rated voltage

kV

12

Rated frequency

Hz

50

Rated insulation level 1 min power frequency withstand voltage pole to earth

kV

42

Rated insulation level 1 min power frequency withstand voltage phase

kV

48

Rated insulation level lightning impulse withstand voltage pole to earth

kV

75

Rated insulation level lightning impulse withstand voltage phase

kV

85

Power frequency withstand voltage of secondary circuit

V

2000

Rated current①

A

630,1250, 1600, 2000, 2500, 3150, 4000, 5000

Rated short-circuit breaking current

kA

20, 25, 31.5, 40, 50

Rated short-time withstand current

kA

20, 25, 31.5, 40, 50

Rated short circuit duration

s

4

Rated peak withstand current

kA

50, 63, 80, 100, 125

Rated short-circuit making current

kA

50, 63, 80, 100, 125

Rated short circuit current breaking times (class E2)

times

30

Rated single/back to back capacitor bank breaking current

A

630/400,  800/400

Clearance between open contacts

mm

11±1

Contact stroke

mm

3~4

Allowable wear thickness of contact

mm

3

Average opening speed

m/s

0.9~1.4

Average closing speed

m/s

0.5~1.0

Contact closing bounce time

ms

≤2

Different phases of contact closing and opening

ms

≤2

Rebound amplitude of opening contact

mm

≤2

Opening time (rated voltage)

ms

20~50

Closing time (rated voltage)

ms

30~70

Mechanical life (M2)

ms

10,000(20,000)

Rated operating voltage

V

AC110/220  DC110/220

Rated operation sequence

O-0-CO-180s-CO

①It is forced cold air when rated current is 4000A

Send Message