0
vacuum circuit breaker

10kV MV Outdoor Vacuum Circuit Breaker/VCB Switch on Pole, ZW20A-12C

EXZW20A-12C
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1.General description

    EXZW20A-12C type AC H.V. vacuum pole automatic controller is used in tri-phase electric system of AC 50Hz, rated voltage 12kV. It can breaking and closing load current, overload current and short circuit fault current, as a device to control and protect electrical network.

2.Main functions

   The controller is an intelligentized device, matches sectionalizer to reach distribution automation without other control system. Consist of circuit breaker (with mechanism operation), controller and control power, besides to opening of closing regular and fault current as circuit breaker, it can repeatedly auto reclosing by advanced setting times for sectionalizer to isolate fault circuits when the short circuit fault happen. The non-fault lines will resume power supply; if repeatedly auto reclosing failed, closing and interlock inside of the controller, another side of network, originally closing and interlock status will remove interlock and auto closing, non-fault lines resume power supply at once. The network automation could limit the power supply interrupted district into minimum range, it has high social benefit and economical benefit

   The product is practical and reliable, multiple functional, the controller uses microprocessor, the panel shown in digital, conveniently with person-machine talking, all the parameters could be adjusted, new function of GPRS communication system could achieve opening, closing operation and teledata communication function by mobile phone, it can transmit lines parameters and running state of the equipment.

   The product adopts EXZW20A-12 type outdoor AC H.V. vacuum circuit breaker as noumenon, the noumenon switching adopts vacuum interrupter to arc extinguishing and SF6 gas to isolate, the case adopts gas sealed, isolation structure technic. No leakiness of internal filling gas, the spring mechanism operation promotes with miniaturization and performance optimization design, operation reliability is more advanced than domestic traditional spring mechanism. Main circuit is sealed inside the case, it has the advantage of anti-explosion, anti-condensation, anti-nasty, no influence by outside environment, it is the first choice on controlling and protecting for intelligent electrical network.

3. Main characteristics

a. Main circuit and mechanism operation of circuit breaker are sealed in SF6 gas, no influenced by outside environment, reaches requirement of free maintaining and long life.

b. It completes a set with electronic controller, to realize remote-control, remote-supervision, remote-signalling, remote-adjusting function, to achieve electrical network intelligent control requirement.

c. New design of miniaturization electromotion spring mechanism, whole spare parts of the product reduced to lowest level, increase the reliability and energy saving of circuit breaker.

d. Fixed with anti-explosion device at the top of case, to avoid leakiness of high temperature gas and splash even if accident occur,ensuring the safe and reliability for the product.

4.Main technical parameter

Item

Unit

Data

Rated voltage

kV

12

Rated frequency

Hz

50

Rated current

A

630,1000

Rated short circuit breaking current

kA

16,20,25

Rated peak value withstand current

kA

40,50,63

Rated short time withstand current (4s)

kA

16,20,25

Rated short circuit making current (peak)

kA

40,50,63

Mechanical life

time

10,000

Rated current breaking times

time

10,000

Breaking times of rated short circuit current

time

30

P.F. withstand voltage (1 min): inter-phase; to earth, fracture

kV

42/48

Lightning impulse withstand voltage; inter-phase; to earth, fracture

kV

75/85

Secondary circuit 1 min power frequency withstand voltage

kV

2

Net weight

kg

140


5.Mechanical property parameter

Item

Unit

Data

Opening distance between contacts

mm

9+1(-0.5)

Contact over travel

mm

3+1(-0.5)

Opening speed

m/s

1.2±0.2

Closing speed

m/s

0.6±0.2

Contact closing bounce time

ms

≤2

Central distance between phases

mm

135±1.5

Insulation distance of outer electrified air

mm

240±2

Outer creepage

cm/kV

3.8

Tri-phase opening asynchronous

ms

≤2

Each-phase conductive circuit resistance

μΩ

≤150

Closing time

ms

≤45

Opening time

ms

≤45

Rated power of energy-stored motor

W

≯40

Rated voltage of energy-stored motor

V

AC220

Rated closing operation voltage

V

AC220

Max./min. closing operation voltage

V

AC264/143

Rated opening operation voltage

V

AC220

Max./min. opening operation voltage

V

AC264/143

Max./min. Motor Voltage

V

AC242/187

Rated pressure of SF6 gas (psig)

MPa

"0"

Send Message