0
vacem load break switch

10kV MV Indoor SF6 Load Break Switch, VFL(R)N36-12kV

EXFL(R)N36-12kV
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description

EXFL(R)N36-12kV indoor M.V. AC load break switch is our company according to the international new technology, and according to the relevant standard of power system in China developed medium voltage switchgear,its performance indicators is full compliance with the IEC420,694,129 and the national standard GB3804-2004 3.6kV-40.5kV M.V. AC Load Switch, GB1985-2004 M.V. AC Disconnectors and Earthing Switches, GB/T11022-1999 Switch Equipment and Control Equipment Standard Shared Technical Requirements, is the main switch components of ring network cabinet.

The indoor load break switch is set closing, opening, grounding for the integration of multi-function medium voltage switchgear, in a fully sealed, epoxy resin shell filled with strengthening to 0.05 MPa of SF6 gas. With a minimum of parts to achieve the above three functions, ensuring that the product quality, improve the reliability. Under normal conditions can be safe operation for more than 20 years with maintenance free.

2. Main technical and characteristic parameter

Item

Unit

Data

Rated voltage

kV

12

Rated frequency

Hz

50

Rated current

A

630

Rated peak withstand current

kA

50

4s rated short time withstand current

kA

20

Rated making current

kA

50

Rated breaking current power load breaking current

A

630

Rated breaking current closed-loop breaking current

A

630

Rated breaking current cable charged breaking current

A

10

P.F. withstand voltage 1min phase to phase, to earth/fracture

kV

42/48

Lightning impulse withstand voltage phase to phase, to earth/fracture

kV

75/85

SF6 gas relative pressure(20℃)

Mpa

≤0.04

Rated operation voltage (electrical operation)

V

AC/DC220

Rated voltage of shunt release

V

AC/DC220

Average opening speed

m/s

3.5±1.5

Average closing speed

m/s

3.5±1.5

Tri-phase opening synchronous

ms

≤3

Main circuit resistance

μΩ

≤120

Manual operation max. Torque

N.m

≤160

Central distance between phases

mm

210±0.5