Item | Unit | Data |
Rated voltage | kV | 24 |
Rated frequency | Hz | 50 |
Rated insulation level 1 min power frequency withstand voltage pole to earth | kV | 65 |
Rated insulation level 1 min power frequency withstand voltage phase | kV | 79 |
Rated insulation level lightning impulse withstand voltage pole to earth | kV | 125 |
Rated insulation level lightning impulse withstand voltage phase | kV | 145 |
Power frequency withstand voltage of secondary circuit | V | 2000 |
Rated current | A | 630,1250, 1600, 2000, 2500, 3150 |
Rated short-circuit breaking current | kA | 20, 25, 31.5 |
Rated short-time withstand current | kA | 20, 25, 31.5 |
Rated short circuit duration | s | 4 |
Rated peak withstand current | kA | 50, 63, 80 |
Rated short-circuit making current | kA | 50, 63, 80 |
Rated short circuit current breaking times (class E2) | times | 30 |
Rated single/back to back capacitor bank breaking current | A | 630/400 |
Clearance between open contacts | mm | 12~14 |
Contact stroke | mm | 3~5 |
Allowable wear thickness of contact | mm | 3 |
Average opening speed | m/s | 1.1~1.6 |
Average closing speed | m/s | 0.6~1.1 |
Contact closing bounce time | ms | ≤2 |
Different phases of contact closing and opening | ms | ≤2 |
Rebound amplitude of opening contact | mm | ≤2 |
Opening time (rated voltage) | ms | 20~50 |
Closing time (rated voltage) | ms | 30~70 |
Mechanical life (M2) | times | 10,000(20,000) |
Rated operating voltage | V | AC110/220 DC110/220 |
Rated operation sequence | O-0.3s-CO-180s-CO |