0
outdoor vacuum circuit breaker

126kV HV Outdoor Self-Evolving SF6 Circuit Breaker, LW36-126

EXLW36-126
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description
  This product is used to control and protect circuit in 126kV and AC 50Hz power system. It could also be used to connect circuit breaker.

2. Product feature
a. Excellent breaking performance of arc-extinguish chamber;
b. Reliable spring operating mechanism;
c. Safe and reliable operation;
d. Less maintenance;
e. High insulation level;
f. Good shock resistance and anti-corrosion capacity.


3.  Main technical parameter

Item

Unit

Data

Altitude

m

1000,2000,3000

Ambient temperature

-30~+40

Rated voltage

kV

72.5      126      256

Rated current

A

2500       3150

Rated frequency

Hz

50

Rated short-circuit breaking current

kA

31.5      40

Rated short circuit making current

kA

80      100

Rated short time withstand current

kA

31.5      40

Rated peak withstand current

kA

80       100

Rated power frequency withstand voltage

kV

To earth:230  fracture:230+73*(reverse pressurization)

Rated lightning impulse withstand voltage

kV

To earth:550  fracture:550+103*(reverse pressurization)

Rated short circuit current duration

s

4

Rated out-of-step breaking current

A

8         10

Line fault breaking current

90%      75%        60%

Rated cable charged making current

A

31.5

Rated operating sequence

O-0.3s-CO-180s-CO

SF6 gas pressure(20℃ gauge pressure)

Mpa

0.6

Mechanical life time

time

6000

Control circuit voltage

V

DC 110 or 220

Creepage distance

mm/kV

25    31

Weight

kg

1500