0
outdoor vcb
outdoor vcb
outdoor vcb

35kV MV Outdoor Vacuum Circuit Breaker/VCB Switch on Pole with Permanent Mechanism, ZW7-40.5kV

EXZW7-40.5kV
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description

EXZW7-40.5kV series outdoor H.V. VCB is electrical appliance equipment with tri-phase AC 50Hz, rated voltage 40.5kV. It is attached to install spring operation mechanism or electromagnetism operation mechanism, can far control electrically operated opening and closing, also can manually store energy, manually opening and closing. The design performance conforms to the national standard requirement GB1984 AC H.V. Circuit Breaker and IEC standard requirement IEC-65 High Voltage AC Circuit Breaker.

EXZW7-40.5 vacuum circuit breaker is mainly used in outdoor 40.5kV power transformer system for control and protection, which is also suitable for normal operation and short circuit protection in the city, the township power distribution network and the industry and mining enterprise. The overall structure of this product is the porcelain insulator column type. The upper porcelain insulator is loaded with vacuum interrupter internal, while the lower porcelain insulator is the prop porcelain insulator, which is suitable for frequent operation place, and has many characteristics, such as good leak-proof quality, anti-aging, withstand high voltage, incombustible, non-explosion, long service life, easy to install and maintain and so on.

2. Main technical parameter

Item

Unit

Data

Rated voltage

kV

40.5

Rated current

A

1600

2000

Rated short circuit breaking current

kA

25

31.5

Rated short circuit making current (peak)

kA

63

80

Rated short-time withstand (thermal stable) current

kA

25

31.5

Rated peak value withstand(dynamic) current

kA

63

80

Rated short-circuit duration

S

4

Rated insulation level lightning impulse withstand voltage (peak)

kV

185

Rated insulation level-1min power frequency withstand voltage dry-type

kV

95

Rated insulation level 1min power frequency withstand voltage wet type

kV

80

Rated operation sequences

O-0.3s-CO-180s-CO

Breaking times of rated short-circuit breaking current

time

20

Full breaking time(to match spring operating device)

ms

≤80

Mechanical life

time

6000

Rated operating voltage

V

220

Opening distance of contact

mm

22±2

Over travel of contact

mm

5±1

Bounce time

ms

≤5

Each phase circuit DC resistance

μΩ

≤120

Outline dimension(length×height×width)

mm

2335×2275×500

Whole weight of circuit breaker and mechanism

kg

1100

Send Message