0
vacuum contactor

6-10kV MV Vacuum Contactor-fuse combination Switch for Switchgear, VACFC

VACFC
Delivery:
FOB
minimum order:
1 piece
Quantity:
Contact Now
add to cart

1. General description

VACYC permanent magnet AC M.V. vacuum contactor and VACFC series AC M.V. vacuum contactor-fuse combination apparatus(F-C) are three-phase AC indoor middle voltage switch device suitable for AC 50-60Hz and the rated working voltage of main circuit is 7.2kV and 12kV. It has the advantages of flexible function combination, compact and reliable structure, multiple protection functions, long service life and allowed frequent operation. It can be widely used to open and close load circuits such as AC motor and transformer, and can also be used for capacitor reactive power compensation.

VACFC series combination apparatus adopt modular combination structure, which can be used by single contactor or combined into F-C, and can be fixed or drawout moving type. The drawout type can be used with KYN28A(GZS1) intermediate cabinet with width of 650mm or 800mm and can be used to replace VSC/P contactor.

VACYC vacuum contactor can be used alone or with other electrical apparatus.

VACYC permanent magnet AC M.V. vacuum contactor and VACFC series AC M.V. vacuum contactor-fuse combination apparatus meet the requirements of national standards GB/T 14808 and GB/T 11022.

2. Main technical parameter

Item

Unit

VACFC

Rated voltage

kV

12

7.2

Rated current

A

25-160

25-315

Rated breaking current

kA

40

Limit breaking capacity

kA

40(100peak value)

Rated transfer current

kA

3.15

1 min rated power frequency withstand voltage

kV

42

32

Lightning impulse withstand voltage

kV

75

60

Power frequency withstand voltage of control circuit

kV

2

Rated operating voltage

V

220V(AC/DC optional)

Operating voltage range

V

75%-100% Ue

Maximum operating current

A

<7.5

Rated current of auxiliary contact

A

5

Life electrical AC3

thousand times

25

Life electrical AC4

thousand times

10

Life mechanical

thousand times

50

Rated operating frequency

times/h

300

Short time operating frequency

20s

600

Closing time

ms

≤40

Opening time

ms

≤35

Average closing speed

m/s

≥0.4

Average opening speed

m/s

≥0.45

Three phase non-simultaneity

ms

≤5

Clearance between open contacts

ms

≥5

≥3.5

Over travel

mm

≥1.5

Main circuit resistance

μΩ

≤150 Not including fuse

Send Message