0
manufacturing vacuum contactor
manufacturing vacuum contactor
manufacturing vacuum contactor
manufacturing vacuum contactor
manufacturing vacuum contactor

1.14kV LV Vacuum Contactor/Switch for Mining and Petrol Field

EXCJ5-1.14kV/63,80,125,250,400,630A
Delivery:
FOB
minimum order:
1 piece
EXELEK EXCJ5 type vacuum contactor is adopted to power network AC 50Hz, the main circuit rated voltage of 600~1140V, rated current from 63A to 630A, for frequently starting and controlling AC motor, forming magnetic starter, and forming anti-explosion magnetic starter.
Quantity:
Contact Now
add to cart

1. General description

   EXELEK EXCJ5 type vacuum contactor is adopted to power network AC 50Hz, the main circuit rated voltage of 600~1140V, rated current from 63A to 630A, for frequently starting and controlling AC motor, forming magnetic starter, and forming anti-explosion magnetic starter.

2. Product images

Type name: EXCJ5-1.14/63A

Type name: EXCJ5-1.14/125A,160A

Type name: EXCJ5-1.14/250A

Type name: EXCJ5-1.14/400A

Type name: EXCJ5-1.14/630A

3. Main technical parameter

Item

Unit

63A

80A

125A

160A

250A

400A

630A

The main circuit rated voltage

kV

1.14

The main circuit rated current

A

63

80

125

160

250

400

630

Main circuit making capacity

A/100times

630

800

1250

1600

2500

4000

6300

Main circuit breaking capacity

A/100times

504

640

1000

1280

2000

3200

5040

Main circuit P.F. withstand voltage

kV

10

Electrical life AC3

Ten-thousand times

60

Electrical life AC4

Ten-thousand times

6

Mechanical lifetime

Ten-thousand times

100

Rated operating frequency AC3

times/h

600

Rated operating frequency AC4

times/h

300

120

Short-time operating frequency(the 20s)

times/h

2000

Clearance between open contacts

mm

1.5±0.1

1.8±0.1

2.0±0.1

2.2±0.1

Over travel

mm

0.8±0.1

1.0±0.1

1.0±0.1

1.0±0.1

Contact circuit P/F. withstand voltage

kV

2

Closing time

ms

≤100

Opening time

ms

≤80

EXCJ5 series EXELEK vacuum contactor can accept customerization different operating voltage:36V,110V,220V,380V etc.
Please inform while ordering.

Send Message