Category
10kV MV Vacuum Contactor/Switch for Capacitor Case and Switchgear, VACG3-12kV-Y
1. General description
This series vacuum contactor consists of electrical insulating frame, metal base, shaft and crank arm, electromagnetic systems, permanent magnet, power modules, auxiliary switches and vacuum interrupters. While control voltage goes across the electromagnetic coil, the armature drives the crutch rotating to open the main contact in the vacuum interrupter. Meanwhile, auxiliary switch cuts off power of electromagnetic coil, turns to be permanent-magnet maintenance. After power broke by control circuit, energy storage power of power module discharges to electromagnetic coil for degaussing, and the main contact broke under the function of opening spring.
The Technical Specifications of this vacuum contactor define its electrical and mechanical parameters for medium-voltage capacitor switching and motor control applications. This mv vacuum contactor series VACG3-12kV-Y consists of electrical insulating frame, metal base, shaft and crank arm, electromagnetic systems, permanent magnet, power modules, auxiliary switches, and vacuum interrupters. The 10kv vacuum contactor operates when control voltage energizes the electromagnetic coil, causing the armature to drive the clutch and open the main contact in the vacuum interrupter. This vacuum contactor features permanent-magnet maintenance mode after the auxiliary switch cuts off coil power. When control circuit power is interrupted, energy storage power of the power module discharges to the electromagnetic coil for degaussing, and the main contact breaks under opening spring force. This mv vacuum contactor is available in rated currents of 160A, 250A, 400A, and 630A for 12kV voltage class. The 10kv vacuum contactor offers making capacity of up to 6300A per 100 operations and breaking capacity of up to 5040A per 25 operations. Each vacuum contactor features power frequency withstand voltage of 42kV, ensuring robust insulation performance. Proper installation of this mv vacuum contactor ensures reliable performance in switchgear and capacitor bank applications.
2. Main technical parameter
Item | Unit | VACG3-160~630/7.2-Y | VACG3-160~630/12-Y | ||||||
Rated voltage | kV | 7.2 | 12 | ||||||
Rated current | A | 160 | 250 | 400 | 630 | 160 | 250 | 400 | 630 |
Making capacity | A/100times | 1600 | 2500 | 4000 | 6300 | 1600 | 2500 | 4000 | 6300 |
Breaking capacity | A/25times | 1280 | 2000 | 3200 | 5040 | 1280 | 2000 | 3200 | 5040 |
Limit capacity | A/3times | 3200 | 4000 | 4500 | 6000 | 3200 | 4000 | 4500 | 6000 |
Power frequency withstand voltage | kV | 32 | 42 | ||||||
Electrical life AC3 | times | 600,000 | |||||||
Mechanical life time | times | 1,000,000 | |||||||
Rated operating frequency | times/h | 300 | |||||||
Short-time operating frequency | times/h | 1000 | |||||||
Mechanical lock operation frequency | times/h | 120 | |||||||
Clearance between open contacts | mm | 4±0.3 | 5±0.5 | ||||||
Over travel | mm | 1.5±0.3 | |||||||
Closing time | ms | ≤30 | |||||||
Opening time | ms | ≤25 | |||||||
Main circuit resistance | μΩ | ≤180 | ≤150 | ≤120 | ≤100 | ≤180 | ≤150 | ≤120 | ≤100 |
Terminal pressure | N | >100 | >100 | >120 | >180 | >100 | >100 | >120 | >180 |