1. General description

VAC83-24kV series vacuum circuit breaker is a new indoor switchgear independently developed by VACEM Co.,Ltd. for 24KV power system.

The optimized modular spring operating mechanism is adopted in the mechanism part, which has high reliability, long service life and free maintenance.

VAC83-24kV series vacuum circuit breaker can be used as the protection and control unit of power equipment for industrial and mining enterprises. It is especially suitable for the worse environment with frequent operation, multiple disconnection of short-circuit.

The Technical Specifications of this 24kV Vacuum Circuit Breaker define its electrical and mechanical parameters for medium-voltage indoor switchgear applications. The VAC83-24kV VCB is a new indoor switchgear independently developed for 24kV power systems, featuring an optimized modular spring operating mechanism that delivers high reliability, long service life, and maintenance-free operation. This Indoor MV Breaker can be used as the protection and control unit of power equipment for industrial and mining enterprises, and is especially suitable for demanding environments with frequent operation and multiple short-circuit interruptions. The 24kV Vacuum Circuit Breaker offers a rated voltage of 24kV and rated frequency of 50Hz, with rated insulation level of 1 min power frequency withstand voltage pole-to-earth of 65kV and phase-to-phase of 79kV. The VAC83-24kV VCB provides lightning impulse withstand voltage pole-to-earth of 125kV, ensuring robust protection against transient overvoltages. This Indoor MV Breaker incorporates advanced vacuum interrupter technology for reliable arc extinction and minimal contact erosion. Each 24kV Vacuum Circuit Breaker undergoes comprehensive routine testing to verify compliance with international standards. Proper installation of this VAC83-24kV VCB as an Indoor MV Breaker ensures long-term operational reliability in 24kV distribution networks.
2. Main technical parameter

Item

Unit

Data

Rated voltage

kV

24

Rated frequency

Hz

50

Rated insulation level 1 min power frequency withstand voltage pole to earth

kV

65

Rated insulation level 1 min power frequency withstand voltage phase

kV

79

Rated insulation level lightning impulse withstand voltage pole to earth

kV

125

Rated insulation level lightning impulse withstand voltage phase

kV

145

Power frequency withstand voltage of secondary circuit

V

2000

Rated current

A

630,1250, 1600, 2000, 2500, 3150

Rated short-circuit breaking current

kA

20, 25, 31.5

Rated short-time withstand current

kA

20, 25, 31.5

Rated short circuit duration

s

4

Rated peak withstand current

kA

50, 63, 80

Rated short-circuit making current

kA

50, 63, 80

Rated short circuit current breaking times (class E2)

times

30

Rated single/back to back capacitor bank breaking current

A

630/400

Clearance between open contacts

mm

12~14

Contact stroke

mm

3~5

Allowable wear thickness of contact

mm

3

Average opening speed

m/s

1.1~1.6

Average closing speed

m/s

0.6~1.1

Contact closing bounce time

ms

≤2

Different phases of contact closing and opening

ms

≤2

Rebound amplitude of opening contact

mm

≤2

Opening time (rated voltage)

ms

20~50

Closing time (rated voltage)

ms

30~70

Mechanical life (M2)

times

10,000(20,000)

Rated operating voltage

V

AC110/220  DC110/220

Rated operation sequence

O-0.3s-CO-180s-CO