Category
24kV MV Indoor Vacuum Circuit Breaker/VCB for Switchgear, VAC83-24kV
1. General description
VAC83-24kV series vacuum circuit breaker is a new indoor switchgear independently developed by VACEM Co.,Ltd. for 24KV power system.
The optimized modular spring operating mechanism is adopted in the mechanism part, which has high reliability, long service life and free maintenance.
VAC83-24kV series vacuum circuit breaker can be used as the protection and control unit of power equipment for industrial and mining enterprises. It is especially suitable for the worse environment with frequent operation, multiple disconnection of short-circuit.
The Technical Specifications of this 24kV Vacuum Circuit Breaker define its electrical and mechanical parameters for medium-voltage indoor switchgear applications. The VAC83-24kV VCB is a new indoor switchgear independently developed for 24kV power systems, featuring an optimized modular spring operating mechanism that delivers high reliability, long service life, and maintenance-free operation. This Indoor MV Breaker can be used as the protection and control unit of power equipment for industrial and mining enterprises, and is especially suitable for demanding environments with frequent operation and multiple short-circuit interruptions. The 24kV Vacuum Circuit Breaker offers a rated voltage of 24kV and rated frequency of 50Hz, with rated insulation level of 1 min power frequency withstand voltage pole-to-earth of 65kV and phase-to-phase of 79kV. The VAC83-24kV VCB provides lightning impulse withstand voltage pole-to-earth of 125kV, ensuring robust protection against transient overvoltages. This Indoor MV Breaker incorporates advanced vacuum interrupter technology for reliable arc extinction and minimal contact erosion. Each 24kV Vacuum Circuit Breaker undergoes comprehensive routine testing to verify compliance with international standards. Proper installation of this VAC83-24kV VCB as an Indoor MV Breaker ensures long-term operational reliability in 24kV distribution networks.
2. Main technical parameter
Item | Unit | Data |
Rated voltage | kV | 24 |
Rated frequency | Hz | 50 |
Rated insulation level 1 min power frequency withstand voltage pole to earth | kV | 65 |
Rated insulation level 1 min power frequency withstand voltage phase | kV | 79 |
Rated insulation level lightning impulse withstand voltage pole to earth | kV | 125 |
Rated insulation level lightning impulse withstand voltage phase | kV | 145 |
Power frequency withstand voltage of secondary circuit | V | 2000 |
Rated current | A | 630,1250, 1600, 2000, 2500, 3150 |
Rated short-circuit breaking current | kA | 20, 25, 31.5 |
Rated short-time withstand current | kA | 20, 25, 31.5 |
Rated short circuit duration | s | 4 |
Rated peak withstand current | kA | 50, 63, 80 |
Rated short-circuit making current | kA | 50, 63, 80 |
Rated short circuit current breaking times (class E2) | times | 30 |
Rated single/back to back capacitor bank breaking current | A | 630/400 |
Clearance between open contacts | mm | 12~14 |
Contact stroke | mm | 3~5 |
Allowable wear thickness of contact | mm | 3 |
Average opening speed | m/s | 1.1~1.6 |
Average closing speed | m/s | 0.6~1.1 |
Contact closing bounce time | ms | ≤2 |
Different phases of contact closing and opening | ms | ≤2 |
Rebound amplitude of opening contact | mm | ≤2 |
Opening time (rated voltage) | ms | 20~50 |
Closing time (rated voltage) | ms | 30~70 |
Mechanical life (M2) | times | 10,000(20,000) |
Rated operating voltage | V | AC110/220 DC110/220 |
Rated operation sequence | O-0.3s-CO-180s-CO |