Category
6-10kV MV Vacuum Contactor/Switch for Capacitor Case and Switchgear
1. General description
VACG series AC vacuum contactor is suitable for power system of AC 50Hz, main circuit rated voltage up to 12kV, rated current up to 630A, for remote making and breaking, frequently starting and controlling AC motors, more suitable for matching with fuse and a variety of protection device to replace vacuum circuit breaker.
The vacem vacuum contactor complies GB/T 14808, IEC 60470 and JB/T 7122 standard, the main performance indicators have reached the international level.
2. Main technical parameter
Item | Unit | VACG-160~630/7.2 | VACG-160~630/12 | ||||||
Rated voltage | kV | 7.2 | 12 | ||||||
Rated current | A | 160 | 250 | 400 | 630 | 160 | 250 | 400 | 630 |
Making capacity | A/100times | 1600 | 2500 | 4000 | 6300 | 1600 | 2500 | 4000 | 6300 |
Breaking capacity | A/25times | 1280 | 2000 | 3200 | 5000 | 1280 | 2000 | 3200 | 5000 |
Rated P.F. withstand voltage | kV | 28 | 42 | ||||||
Mechanical life time | times | 1,000,000 | |||||||
Rated operating frequency | times/h | 300 | |||||||
Short-time operating frequency(20s) | times/h | 1000 | |||||||
Mechanical lock operation frequency | times/h | 120 | |||||||
Clearance between open contacts | mm | 4±0.2 | 6±0.5 | ||||||
Over travel | mm | 1.8±0.2 | 1.8±0.2 | ||||||
Closing time | ms | ≤80 | |||||||
Opening time | ms | ≤40 | |||||||
Main circuit resistance | μΩ | ≤200 | |||||||
Tri-phase asynchronous time | ms | ≤2 | |||||||
Send Message